    A unit for professional mining fit for 24 Antminer. This rig is made for those who want to intensively expand their mining operation.
    Tank with
    hydraulic strapping
    Distribution board and
    power units
    Casing for miners
    Circulator pump
    Brazed plate
    heat exchanger
    Heat carrier
    SPECIFICATIONS DESCRIPTION PHOTOS DOCUMENTS DELIVERY
    Maximum cooling capacity
    66 kW
    Optimal water consumption for 10 kW
    0.2 m³/h
    Electrical connection
    5x35 mm² (copper conductors)
    Water connection
    3/4 inch minimum (for tap water)
    Power consumption per pump
    0,345 kW
    Tank capacity
    330 l
    Assembled weight (without coolant)
    145 kg
    Dimensions with lid (LxWxH)
    1825х1100х800mm
    Detailed description and instructions The unit comes in two versions, with engine compartment either on the left or the right side of the device.This unit is designed for heat removal of 240 MJ or 66 kW / h of electricity. For example, 24 Antminer S9 x 2.5 kW (el. power considering overclock) = 60 kW. The unit itself consumes 0.345 kW on the circulation pump. It is connected to a source of cold water below 20 degrees Celsius. Tap water can be used, as well as, water from a reservoir (river, pond, lake), a well or a closed circuit, which presents lots of options (pipes laid in the ground, return of tap water to the water main through a bypass, heating of water intake, etc.). During routine operation below 60 kW/h, approximately 1.2 m³ of water per hour is required. Elecricity wise, the unit connects with a 35 mm² x 5 copper core cable. It is also possible to use two 16 mm² x 5 copper core cables, or three 6 mm² x 5 cables, parallel connection. In the distribution board, the cable is protected by a 100 amps automatic circuit-breaker and an RCD, or a 100 amps differential circuit-breaker. In the unit's stock board the cable is connected to three contactors (one contactor per phase) that switch power for miner's circuit-breakers. 24 circuit breakers in total, 1 per miner. The board also features control chain circuit breakers, a pump, and a unit with four additional sockets for connecting a network commutator, a computer, etc. Elecricity wise, the unit connects with a 35 mm² x 5 copper core cable. It is also possible to use two 16 mm² x 5 copper core cables, or three 6 mm² x 5 cables, parallel connection. In the distribution board, the cable is protected by a 100 amps automatic circuit-breaker and an RCD, or a 100 amps differential circuit-breaker. In the unit's stock board the cable is connected to three contactors (one contactor per phase) that switch power for miner's circuit-breakers. 24 circuit breakers in total, 1 per miner. The board also features control chain circuit breakers, a pump, and a unit with four additional sockets for connecting a network commutator, a computer, etc. Water wise, the unit conects with a flexible flow pipe. The heat exchanger nozzles have a 2" external rifling, so, depending on the cooling option you choose, adapter couplings may be required. A 3/4" flexible flow pipe is enough to connect to a main water supply. In other cases we will consult you if needed. It is advisable to put a mesh filter for primary water refining and a valve for smooth adjustment of water flow to the heat exchanger. Volume of cold water supplied determines temperature of the coolant in the unit. Recommended coolant temperature is 50-65 degrees Celsius (for Antminer S9, may vary depending on hardware). The unit comes equipped with overheat protection. The thermostat is set to 68-72 degrees. When the unit heats up to 72 degrees it shuts down. After cooling down to 68 degrees it will turn on automatically. The user is able to change values of those thresholds, however it is ill-advised to set them above 80 degrees. The unit also features a system that automaticaly turns it off when level of coolant in the tank is lower then critical.
    Contact us if you need delivery beyond Russian Federation.